Carbon dioxide detector KB-502 is applied to detect the carbon dioxide concentration in industrial, agricultural or dwelling environment, and monitor the interior temperature and humidity. 1~3 ways 0~10V analog quantity and three-way relay electronic contact signals output, can control the controlled devise directly or be transmitted in to any electronic analog controllers. Autonomous system of DDC/PLC controller or draft apparatus can monitor the draft system based on the detection target value (CO2 concentration, temperature and humidity).
KB-502 has RS-485 communication interface which can connect to the computer or other control system with independent addressing, to accomplish the intelligent management for the draft system of each room.
Widely be used for ventilation controlling in industrial and agricultural environment (such as workshop, greenhouse, clean room, etc), public place (such as hotel, exhibition hall, hospital, department store, bar, restaurant, airport, railway station, cinema, etc) and other place (villas, office, meeting room, class room, etc).
Features
• Real-time monitor the CO2 concentration, detecting range 0~20,000 PPM (0~50,000 PPM is optional);
• USA Telaire sophisticated NDIR infrared self diffusion sensor which has long performance life of 15 years;
• ABC Logic self-setting patented technology, user need not to set it repeatedly during long time usage;
• Microprocessor-based programmable on-site settings with rapid response
• Three-wire system 4~20mA standard signals output and long-distance transmission;
• PC/ABS high quality fire retardant material housing;
• CE standard certificate.
Technical Specifications
Applicable gas | Carbon dioxide (CO2) |
Sensor | NDIR infrared CO2 sensor with long performance life of 15 years |
Accuracy | ±30 PPM+3% reading (For 5°C, 2000 PPM) |
Stability | 2% |
Calibrating Period | ABC Logic automatic calibration (user need not make separate calibrations) |
Nonlinearity | <1% (F.S) |
Response Time | <2mins (For a change within 90%) |
Signals Refreshing Frequency | 2 seconds |
Preheat Time | 24 hours (for first use) 10mins (for everyday use) |
Detecting Range | Wall-mounting: 0~2000 PPM, 0~5000 PPM, 0~20000 PPM Pipeline type: 0~2000 PPM |
Resolution | 1 PPM |
Airflow Rate | Self-diffusion type: 80~120 cc/min ( wall-mounting) Influent type: 40~50 cc/min (pipeline type) |
Power Supply | 24V AC / 24V DC |
Power Consumption | 3.5W (maximum), 2.8W (average) |
Analog Quantity Output | Linear output corresponding to CO2 detecting value: 0~10V AC / 4~20mA (optional) |
Operating Environment | Temperature: 0~50°C Humidity: ≤85%RH (non-condensing) |
Storage Temperature | -40~70°C |
Weight | 180g |
Dimensions | 124mm*70mm*45mm |
Installation | terminal box (65mm*65mm / 2inch *4inch) |
Certificate | CE standard |